CH0808 Explosion Proof Isolating Switch

Main Technical Data
  • Explosion-proof Mark: Ex db eb II C Gb
  • Application Zone: Zone 1 & Zone 2
  • Ambient Temperature: -40℃ ~ +60℃
  • Operating Temperature: -40℃ ~ +75℃
  • Compliance Standards: Ex, GB/T3836.1
  • Module Poles: 2, 3, 4, 6 poles
  • Models & Rated Current:CH0808-25A: 25ACH0808-40A: 40ACH0808-80A: 80A
  • Rated Insulation Voltage Ui: 800V
  • Rated Impulse Withstand Voltage Uimp: 6kV
  • Rated Short-time Withstand Current Icw:3kA (25A, 40A); 10kA (80A)
  • Rated Short-circuit Making Capacity Icm:4kA (25A, 40A); 17kA (80A)
  • Fuse Short-circuit Protection:20kA 500V/35A (25A)20kA 500V/63A (40A)50kA 500V/160A (80A)
  • Fuse Protection Characteristic: gG (Compliant with IEC/EN60269-1)
  • Terminal Wire Cross-section:25A: 2×1.5~4mm²
    40A: 2×10mm²

    80A: 2×16~25mm²

  • Housing Material: Unsaturated Polyester Resin
Guaranteed Safe Checkout
Overview
  • The isolating switch features excellent flame retardancy.
  • The switch module adopts a spring energy storage instant release acceleration mechanism for rapid make-and-break operation.
  • The contact material of the isolating switch module is silver alloy; all wire pressing screws at wiring terminals are stainless steel.
  • The isolating switch module provides large clearance distance.
  • This product must be used in conjunction with increased safety enclosures; it cannot be used alone in flammable explosive gas atmospheres.
  • Operating handle with IP66 protection rating